 |
Technical
SErvices |
 |
|
Vacuum Testing Precast
Concrete Manholes
Vacuum testing is a quick, safe and practical
way to validate manhole system integrity. Manhole sections
can be tested at the precast concrete plant prior to delivery
or on site prior to backfilling. Here you will find not only
how to perform vacuum testing, but you will discover the benefits
and limitations of vacuum testing as well.
Please follow the links to your preferred
topic:
Measuring Pressure
Creating a Vacuum
When to Vacuum Test
ASTM C1244
Vacuum Testing in the Presence of
Ground Water
Adjusting Vacuum Pressure
APPENDIX (Supplemental Information)
Disclaimer
Measuring
Pressure
Having a general knowledge and understanding
of atmospheric pressure and hydrostatic pressure is essential
when performing a vacuum test in the field.
Atmospheric Pressure
Atmospheric air, or the air we breathe,
is a gas composed primarily of nitrogen molecules (80 percent)
and oxygen molecules (16 percent) that are bound to the earth
by gravitational forces. Atmospheric pressure is defined as
the force per unit area exerted against a surface by the weight
of the air above that surface. Thus the atmospheric pressure
varies with altitude above the earth’s surface. Atmospheric
pressure at sea level is 14.67 pounds per square inch (psi).
An alternative system of measurement
(inches of mercury) is derived from the way in which atmospheric
pressure is typically measured. If we insert one end of a
vacuum-filled tube (see Figure 1) into a liquid and allow
the liquid free access to the atmosphere, then the liquid
will rise up the tube until the force exerted by the weight
of the liquid column balances the atmospheric pressure. The
denser the liquid used, the lower the height of the column.
In initial experiments, liquid mercury (Hg) was used, and
the corresponding column height was found to be 29.92 inches
of mercury. (If water had been used, the column would be 408
inches – 34 feet – high.) The following relationships
can be used to convert atmospheric pressure between the units
of inches of mercury (in Hg) and pounds force per square inch
of area (psi):

Gauge
Pressure
Most industrial gauges work on the Borden tube principal,
which pressurizes a closed, curved tube and measures how much
the tube tries to straighten out. The curved tube is surrounded
by the atmosphere and therefore has 15 psi resisting the tendency
to straighten. The gauge therefore measures the difference
between the internal pressure trying to straighten the tube
and the atmospheric pressure acting to resist the straightening.
So if we read 35 psi on the gauge, there is really
50 psi being applied.
Normally we do not take atmospheric
pressure into consideration in our everyday lives, since it
surrounds us uniformly and universally – the same 15
psi exists internally as well as externally, creating a state
of equilibrium as illustrated in Figure 2. However, to differentiate
between the two measuring systems, we add the word “gauge”
to measurements referencing atmospheric pressure as the zero
point (i.e., psig) and the word “absolute” to
measurements referencing full vacuum as the zero point (i.e.,
psia).
Figure
2: Manhole Prior to Backfill
Hydrostatic Pressure
The pressure created by a fluid is
a function of the fluid’s unit weight
and the height (h) of the liquid column above a reference
plane. Water, for example, has a unit weight of 62.4 pounds
force per cubic foot, which corresponds roughly to 0.43 psig
per foot of water column height. The pressure created by a
23-foot water column is roughly 10 psi gauge (psig) or 25
psi absolute (psia). Following are a series of expressions
that illustrate the relationship between the unit weight of
water and its corresponding gauge pressure per foot of water
column height and the example solution for the pressure created
by a 23-foot water column.

Example:

Back to top
Creating
a Vacuum
Vacuum is defined as an absence of matter (molecules) in a
defined volume of space.
To produce a vacuum in the field we need to remove all the
molecules of matter (air) from within an enclosed space (manhole
structure). Initially a manhole which has not been backfilled
is uniformly loaded by atmospheric pressure (15 psia) on its
interior and exterior, creating an equilibrium state. To create
a vacuum we use a pump, or venturi nozzle, attached to the
manhole and attempt to “suck” out the air. It
is almost impossible to produce a total vacuum. The closer
we get to a full vacuum (29.92 inches Hg) the harder it gets
to encourage the remaining molecules to leave.
In reality all we do is create a partial
vacuum (somewhere between 0 inches Hg and 29.92 inches Hg),
which in turn creates a pressure differential between the
partial vacuum inside the manhole and the atmospheric pressure
pressing against the exterior of the manhole.
When a vacuum of 10 inches Hg is
drawn on a manhole, an internal pressure of roughly -5 psig,
or 10 psia, is created. The atmospheric pressure on the exterior
of the manhole (15 psia) will thus exert 5 psi differential
pressure on all surfaces, joints and connectors as illustrated
in the following animation. No other test method uniformly
tests a structure in this way.
Click
to view an illustration of a Vacuum Test prior to backfill
Back to top
When
to Vacuum Test?
Many codes and specifications require that a vacuum test be
performed after the manhole has been installed and backfilled.
Testing after backfilling provides a degree of certainty that
a watertight system has been installed. The major disadvantage
is the fact that no industry standards exist for
vacuum testing after the structure has been backfilled. Secondly,
it is often difficult to determine the cause or locate and
repair a system breech once the manhole has been backfilled.
The resolution to this problem is
to perform a vacuum test prior to backfilling and, if necessary,
again after backfilling.
Click here for Appendix
A: Suggestions for detecting leaks
ASTM
C1244
ASTM C1244, “Standard Test Method for Concrete Sewer
Manholes by the Negative Air Pressure (Vacuum) Test Prior
to Backfill,” has been developed to govern the proper
vacuum testing procedure for testing concrete manholes. ASTM
C1244 clearly states that a vacuum test “is intended
to be used as a preliminary test to enable the installer to
demonstrate the condition of the concrete manhole prior to
backfill.”
When utilizing ASTM C1244, a vacuum of 10
inches Hg is drawn on the manhole after all lift holes are
plugged, and pipes entering the manhole are temporarily plugged
and securely braced. The time is measured for the vacuum to
drop to 9 inches Hg. The manhole is accepted if the measured
time meets or exceeds the values presented in Table 1 of ASTM
C1244. If the manhole fails the initial test, it may be repaired
by an approved method until a satisfactory test is obtained.
Note: The latest edition of ASTM
C1244 shall be used for proper testing procedures and criteria.
Vacuum
Testing in the Presence of Ground Water
Vacuum testing after backfilling should be performed only
after a successful non-backfill test has been completed in
accordance with ASTM C1244.
CAUTION
Many people do not fully understand the
effects of vacuum testing backfilled manhole systems in the
presence of ground water. Vacuum testing backfilled manhole
systems is not recommended, especially in the presence of
ground water. Vacuum testing a manhole system that is already
subjected to hydrostatic pressure may exceed the design limits
of critical flexible connectors leading to a system failure.
If ground water is present, use the following
information to determine if a reduction in vacuum pressure
is warranted:
Note: For simplicity, the effects
of soil pressure are not taken into account in the following
information and examples. In reality, the actual in-place
loads may be greater when in-place soil conditions (effective
stress) are taken into consideration. To determine the actual
loads induced on a backfilled structure, use the following
information in addition to the actual in-place soil properties
to properly calculate the effective stress at the critical
location.
- Depth to water
table
- Pressure rating
for flexible connector
- Depth to bottom-most critical connector
With this information, you can determine
the theoretical in-place loads experienced by the deepest
connector as outlined in the following example. If the combined
pressure differential (vacuum and hydrostatic) between the
interior and exterior of the manhole exceeds the connector’s
pressure rating, appropriate adjustments must be made.
Example: XYZ County specifications require
that all manhole systems be vacuum tested in accordance with
ASTM C 1244 requirements except they test after backfill.
Manhole Diameter: 48 inches
Manhole Depth: 30 feet
Depth to Water Table: 8 feet
Acceptance Test: ASTM C 1244*
Resilient Connector: ASTM C 923**
Depth to Connector: 28 feet
* ASTM C 1244 requires a vacuum between 10 inches Hg and 9
inches Hg (-5 psig to -4.5 psig) be maintained for 74 seconds.
** ASTM C 923 requires resilient connectors to withstand a
hydrostatic pressure of 13 psig when installed in a straight
alignment and 10 psig when axial deflected 7 degrees.
External Pressure at Critical Depth (Hydrostatic
pressure)
Click here
for an illustration of the “Effects of Hydrostatic Pressure
on a Backfilled Manhole”
Internal Pressure at Critical Depth (Vacuum
pressure)
Click here
for an illustration of the effects of a “Vacuum Test
on a Backfilled Manhole Already Subjected to Hydrostatic Pressure”

Does the Pressure Differential Exceed the
ASTM C 923 Pressure Rating?

The combined vacuum test and in-place
hydrostatic loads exceed the connector’s pressure rating
so appropriate adjustments must be made.
Back to top
Adjusting
Vacuum Pressure
Most flexible connectors have a pressure rating of only 10
psi when deflected, which is fairly common in a field installation;
therefore we will use the more conservative 10 psi pressure
rating as a base point. Drawing a vacuum of 10 inches Hg creates
a pressure differential of 5 psi between the interior and
exterior of a manhole system. A water column of 11.5 feet
creates an additional 5 psi of external pressure. This ultimately
creates a pressure differential of 10 psi at a connector
located 11.5 feet under water when drawing a vacuum of 10
inches Hg.
A conservative rule of thumb is to
reduce the vacuum by 1 inch Hg for every 1 foot of hydrostatic
head between 12 feet and 21 feet. A vacuum test should not
be performed when the hydrostatic head exceeds 22 feet.
| Hydrostatic Head (ft)* |
12 |
13 |
14 |
15 |
16 |
17 |
18 |
19 |
20 |
21 |
22 |
| Vacuum Pressure (in Hg) |
10 |
9 |
8 |
7 |
6 |
5 |
4 |
3 |
2 |
1 |
** |
| * Hydrostatic head above critical connector |
| **At 22 feet below the groundwater table,
the connector is naturally subjected to 9.5 psi |
Above Example Continued
Using the recommendation above, the testing
agency should draw only 2 inches Hg to prevent overloading
the flexible connector as illustrated in Figure 3.
External Pressure at Critical Depth (Hydrostatic
pressure)

Internal Pressure at Critical Depth (Adjusted
Vacuum pressure)
Click
here to view an illustration of vacuum reduction
Back to top
APPENDIX
(Supplemental Information)
A.
Detecting Leaks:
Prior to Backfilling:
Leaks, though rare, can be readily detected by finding the
source of the hissing sound as air enters the manhole. Leaks
can also be detected by spraying water on the exposed wall
surface – infiltrating air will produce a dry spot.
If the manhole fails the initial test, make repairs and retest
until obtaining a satisfactory test.
After Backfilling:
Leaks can be detected by spraying a soapy solution on the
interior of the manhole. Solutions of 2 to 10 ounces of liquid
soap per gallon have been recommended for ambient temperatures
below 80 degrees F (27 degrees C). A similar solution with
a few ounces of corn syrup is recommended for temperatures
above 80 degrees F (27 degrees C). Bubbles will form at leaks.
If the manhole fails the initial test, make repairs and retest
until a satisfactory test is obtained. When adequate repairs
cannot be made from the interior, exterior repairs should
be made by means of excavation.
B.
Stand Pipes:
The presence of ground water near a manhole
can have a significant effect on the performance of a manhole
system during a vacuum test as outlined above. To avoid damaging
the installed system, an accurate measurement of the water
table is required to account for hydrostatic loads. Install
a stand pipe alongside the manhole stack during the backfill
process. Once dewatering operations cease and the water table
stabilizes, measure the water level by lowering a chain or
measuring tape into the stand pipe.
C.
Pressure Ratings:
ASTM pressure ratings shall be used unless
the manufacturer provides sufficient data indicating a higher
rating.
ASTM C 923, “Standard Specification
for Resilient Connectors Between Reinforced Concrete Manhole
Structures, Pipes and Laterals”
This specification covers the minimum
performance and material requirements for resilient connectors
used for connections between reinforced concrete manholes
conforming to Specification C478 and pipes, between wastewater
structures and pipes, and between precast reinforced concrete
pipe laterals.
This specification requires that resilient
connectors withstand 13 psi of hydrostatic pressure for
straight aligned pipes and 10 psi of hydrostatic pressure
for axial deflected pipes and laterals.
ASTM C 1478, “Standard Specification
for Storm Drain Resilient Connectors Between Reinforced Concrete
Storm Sewer Structures, Pipe, and Laterals”
This specification covers the minimum
performance and material requirements for resilient connectors
used for connections between precast reinforced concrete
storm sewer structures conforming to Specification C 478
and pipes, and between precast reinforced concrete pipe
and laterals for storm drainage systems.
This specification requires that
resilient connectors withstand 6 psi of hydrostatic pressure
for straight and axial deflected pipes and laterals.
D. Other Test Methods
Prior to the introduction of vacuum testing,
manholes were typically tested for watertightness in accordance
with:
ASTM C 969, “Standard Practice
for Infiltration and Exfiltration Acceptance Testing of Installed
Precast Concrete Pipe Sewer Lines”
ASTM C 924, “Standard Practice
for Testing Concrete Pipe Sewer Lines by Low-Pressure Air
Test Method”
ASTM C 969 may take up to 72 hours
or more to complete, while ASTM C 924 presents a potential
safety hazard if the line is not prepared properly and if
procedures are not followed. Test pressures must also be adjusted
to account for groundwater tables when using ASTM C 924 with
a maximum testing limit of 5 psi gauge pressure, in which
case ASTM C 969 is to be used. ASTM C 969 also has limitations
in the fact that the structure is not uniformly tested.
Disclaimer
The above information
is intended solely for use by professional personnel who are
competent to evaluate the significance and limitations of
the information provided herein, and who will accept total
responsibility for the application of this information. The
National Precast Concrete Association (NPCA) disclaims any
and all responsibility and liability for the accuracy and
application of the information.
Back to top
|